THE AIR QUALITY AND THERMAL COMFORT IN A WOMEN’S FITNESS CENTER IN BANDA ACEH
DOI:
https://doi.org/10.24191/myse.v13i2.9587Keywords:
Air Quality, Thermal Comfort, Fitness Center, Banda Aceh CityAbstract
This study aims to evaluate the current air quality conditions and temperature comfort at the Zumba Wawa Barata women's fitness centre in Banda Aceh. The method used is quantitative descriptive through direct field measurement of temperature, air humidity level, CO₂ content, PM₂.₅ concentration, and calculation of the Wet Bulb Globe Temperature (WBGT) index, accompanied by a survey of user comfort perceptions. Measurement results show that the temperature in the gym and exercise room reaches 35–39 °C, exceeding the ASHRAE 55 comfortable standard, which sets the range at 22–26 °C. The humidity level is recorded in the range of 50–70%, slightly exceeding the ideal limit of 30–60%, while the CO₂ level (381–435 ppm) is still within the safe threshold of ASHRAE 62.1 (≤1000 ppm). PM₂.₅ concentration experiences a drastic surge to >800 µg/m³ during peak hours (16:00–18:00), far exceeding the WHO standard of 25 µg/m³ (24 hours) and indicating very unhealthy air quality due to the accumulation of dust particles, sweat, and a less-than-optimal air circulation system. The WBGT index shows a value of 28–30.7 °C, exceeding the NIOSH limit of 26–28 °C, indicating a risk of heat stress during moderate to high-intensity activities. The conclusion of this study indicates that the air quality and temperature comfort conditions at the fitness centre do not yet meet health and comfort standards. The recommendations provided include improving the natural and mechanical ventilation systems, regulating the number of participants per training session, and regularly monitoring air quality to create a healthy and comfortable exercise environment for women.
References
Chao, C. Y. H., et al. (2021). Effects of indoor air quality and ventilation on occupant performance and health. Science of the Total Environment, 754, 142233.
Geng, Y., Ji, W., Lin, B., & Zhu, Y. (2021). CO₂ and comfort: Evidence from energy-efficient buildings in China. Energy and Buildings, 236, 110771.
Hussain, A., et al. (2022). Analysis of thermal comfort and indoor air quality in gymnasiums. Applied Thermal Engineering, 198, 117546.
Sugiyono. (2019). Metode Penelitian Kuantitatif, Kualitatif dan R&D. Bandung: Alfabeta.
Wargocki, P., Wyon, D. P., & Fanger, P. O. (2020). The performance and well-being of schoolchildren in classrooms with different ventilation rates. Indoor Air, 30(3), 452–464.
Yang, B., et al. (2020). Impact of ventilation strategies on indoor air quality and energy consumption in fitness centers. Building and Environment, 180, 107021.
Zhang, H., Arens, E., & Zhai, Y. (2022). Thermal comfort in naturally ventilated buildings in hot climates. Indoor and Built Environment, 31(3), 387–400.
Downloads
Published
Issue
Section
License
Copyright (c) 2026 Rizki Putri Pona, Laina Hilma Sari, Irin Caisarina

This work is licensed under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License.
Myse journal is a scholarly online, open access, peer reviewed journal.
Started in June 2023, the Malaysian Journal of Sustainable Environment is licensed under CC BY-NC-ND 4.0